PS40-Extended
Made in UAE
Lasting quality and durability
10 sec - 3 min Delay Timer
Smart timer algorithm inside
Smart Chip
Delivering 7 types of power protection
Preventing Fire Incidents
Keeping you and your loved ones safe
Meet Powermatic
Micro Automation Industries developed Powermatic, the new concept in power protection, it connects load only after a comprehensive monitoring of electrical supply and when the supply is within the specified parameters. It continues monitoring and disconnects when there are any disturbances, thus it avoids expensive damage and breakdown to connected equipment.
Powermatic, as a microprocessor embedded solution, provides the smartest comprehensive detection and reaction response to more than one power disturbances at low cost.
Powermatic, as a microprocessor embedded solution, provides the smartest comprehensive detection and reaction response to more than one power disturbances at low cost.
Working Principle
After the main power supply (Mains) is switched ON, Powermatic will monitor the Mains and withhold it from reaching the connected equipment. If the Mains is stable (Yellow state), Powermatic continues to monitor the power quality for a certain determined time.
If the power quality is within the limits, Powermatic will then connect Mains to the equipment (Green state). However, Powermatic will continue to monitor power quality.
Powermatic disconnects whenever it detects power disturbances beyond preset limits (Red state).
When Mains resumes stable, Powermatic continues monitoring the power quality and reconnects Mains to the equipment after determined time.
If the power quality is within the limits, Powermatic will then connect Mains to the equipment (Green state). However, Powermatic will continue to monitor power quality.
Powermatic disconnects whenever it detects power disturbances beyond preset limits (Red state).
When Mains resumes stable, Powermatic continues monitoring the power quality and reconnects Mains to the equipment after determined time.
STOPS 7 TYPES
OF POWER DISTURBANCES
Built to a Sustainable Solution
Product Specifications
Type | PS40-25 | PS40-26 |
---|---|---|
Power Standard | 230V ~ 50Hz | 220V ~ 60Hz |
Continuous Load Current | 40 A | |
Waiting Time | Smart Timer(1/2 - 3 minutes) | |
Over Voltage Connect | 255V | |
Under Voltage Connect | 180V | |
Interruption Response Time | 20 millisec. | |
Under Frequency | 46Hz | 56Hz |
Over Frequency | 54Hz | 64Hz |
Max. Supply | 420V | |
Surge Response Time | <10ns | |
Surge Clamping Voltage | 1120@25 Ampere(8/20 µs surge) | |
Max. Ambient Temperature | 55°C, 80% Humidity | |
Enclosure Protection | IP20 | |
Safety Standard | LVD 73/23/EEC, IEC 60669-1 | |
Life Test | 10,000 times@240V 40A 0.6PF | |
Wall Mounting Box | Standard box | |
Connection Type | Screw terminal | |
Unit Weight | 125 gm | |
Unit Dimension(H x W x D) | 81x 81 x 35 mm | |
Packing Option | Blister Shell(BS) |